CF Nano2 2025

Compact CO2 systems for small cooling capacities

The [CF] NANO2 series was designed for applications with low cooling capacity – ideal for gastronomy, hotels, and retail.

  • Redundancy through compound design
  • Flexible Installation – lndoor & Outdoor
  • Designed for minimal partial loads
  • Carel, Danfoss, or Wurm control technology
  • Active oil management
  • Compact construction
  • Suitable for cold rooms under 1.5 kW
  • Maintenance-friendly
CF NANO₂ CO2 system for gastronomy and hotels CF SYSTEMS

Why [CF] NANO₂?

The robust system for minimal partial load is often underestimated

When designing refrigeration systems, the focus is often on maximum cooling capacity – although this is only actually needed for a few hours a year. Most of the time, the system operates in partial load, which is often neglected in planning and poses technical challenges, especially for CO systems in the lower performance range.

Planning for minimal cooling load is crucial

Therefore, the following aspects should be considered already in the project planning phase:

  • Cold room operation in partial load: Which cold rooms could run individually?
  • Real minimum cooling load: Lowest expected utilization.
  • Low-load periods: Times with low demand (e.g., at night, outside of use).
  • Influence of outside temperature: Higher partial load capacity at cool outside temperatures.

System design makes the difference

In the lower performance range, partial load is often not considered – typically, plug & play units with single-compressor design are used here. However, due to their design, these are only suitable to a limited extent for the challenges of partial load operation. The compound design of the [CF] NANO2, on the other hand, enables:

  • a significantly lower partial load with the same maximum capacity
  • increased operational reliability through multiple compressors

Active oil management for maximum safety

  • If the minimum partial load is not safely dissipated, the compressors cycle. The consequences: high wear, oil carry-over, and oil deficiency – a common cause of failure in plug & play units in systems with low partial load.
  • The [CF] NANO₂ protects itself: Active oil management detects oil deficiency early, automatically switches off the compressor, and ensures optimal oil filling – for continuous operational reliability.

Technical data

Type[CF] NANO₂[2×0] 2×0[7]X[Do]1V14[CF] NANO₂[2×0] 3×0[13]X[Do]1V14[CF] NANO₂[2×0] 5×0[18]X[Do]1V14[CF] NANO₂[3×0] 4×0[11]X[Do]1V14[CF] NANO₂[3×0] 5×0[21]X[Do]1V14[CF] NANO₂[3×0] 7×0[25]X[Do]1V14
Order No. Carel182-2110182-2111182-2112182-2120182-2121182-2122
Order No. Danfoss182-2130182-2131182-2132182-2140182-2141182-2142
Min. capacyity1.40 kW1.84 kW3.31 kW1.40 kW2.49 kW3.31 kW
Max. capacity2.94 kW4.56 kW6.96 kW5.07 kW7.73 kW10.09 kW
Gas cooler capacity5.03 kW7.95 kW11.96 kW8.57 kW13.31 kW17.13 kW
Number of compressors222333
receiver volume14 l14 l14 l14 l14 l14 l
discharge line connection⅜”⅜”⅜”¾”¾”¾”
Gas cooler return line⅜”⅜”⅜”¾”¾”¾”
Liquid line⅜”⅜”⅜”¾”¾”¾”
Suction line⅜”⅜”⅜”¾”¾”¾”
PS HP120 bar120 bar120 bar120 bar120 bar120 bar
PS MP90 bar90 bar90 bar90 bar90 bar90 bar
PS NP90 bar90 bar90 bar90 bar90 bar90 bar
Sound pressure level at 10 m33.5 dB(A)34.5 dB(A)36 dB(A)35.6 dB(A)36.8 dB(A)37.8 dB(A)
Max. operating current6.3 A8.3 A14.3 A10.7 A14.8 A20.3 A
weight354 kg360 kg363 kg404 kg412 kg415 kg
Gas cooler typeGW30E213AF001GW30E213AF001GP45C114BF001GW30E213AF001GP45C114BF001GP45C114BF001
Order No..185-1088185-1088185-1089185-1088185-1089185-1089
Air discharge directionhorizontalhorizontalhorizontal & verticalhorizontalhorizontal & verticalhorizontal & vertical
Sound pressure level at 10 m40 dB(A)40 dB(A)42 dB(A)40 dB(A)42 dB(A)42 dB(A)
Connections (inch)Ø ¾ K65Ø ¾ K65Ø ¾ K65Ø ¾ K65Ø ¾ K65Ø ¾ K65
Length x width x height1152 × 316 × 5331152 × 316 × 533981 × 646 × 7531152 × 316 × 533981 × 646 × 753981 × 646 × 753
Weight28 kg28 kg63 kg28 kg63 kg63 kg

* The capacity is calculated at: t0 -10 °C, GKaus 38 °C and 93 bar
** incl. control cabinet
***without pipe outlets

 

Scope of delivery

  • 2 to 3 MT compressors (transcritical)
  • Capacity control of the MT lead compressor via VFD
  • Active oil management
  • Receiver (14 l)
  • Service and shut-off valves on all service-relevant pipe sections
  • Pressure and temperature sensors matched to the respective control manufacturer
  • high-quality insulation with Armacell AF
  • All pipe outlets (CuFe2P) are routed to the rear.
  • Pressure-resistant design (HD= PS120, all others PS90)
  • fully welded base plate including vibration dampers
  • Control cabinet, assembled, wired, and pre-programmed
More content

Options

  • Housing for indoor and outdoor installation without sound insulation, supplied loose
  • Heat recovery with 3-way valve, supplied loose
  • Filter drier, supplied loose
  • Gas cooler, supplied loose
More content

Control & control cabinet

  • Carel μRack CO2, Danfoss AK-PC 572A, Wurm DCO2-BL (on request)
  • Main switch
  • Control transformer
  • Power supply for closing the HP and MP valves in the event of power failure
More content

Dimensional drawing

CF NANO₂ Maßzeichnung CF SYSTEMS