Installation through
standard door dimensions
Performance range
from
20…200kW*
10…120kW*
Technical data
| Frame size | 2 x 2 | 3 x 3 | 4 x 4 | 5 x 4 | 6 x 4 |
|---|---|---|---|---|---|
| Number of MT compressors | 2 | 3 | 4 | 5 | 6 |
| Number of LT compressors | max. 2 | max. 3 | max. 4 | max. 4 | max. 4 |
| Length in mm ** | 2,880 | 3,330 | 4,090 | 4,540 | 4,990 |
| Width in mm | 800 | 800 | 800 | 800 | 800 |
| Height in mm *** | 1,960 | 1,960 | 1,960 | 1,960 | 1,960 |
* Performance calculation based on evaporation temperatures:
–8 °C MT, –30 °C LT and 37 °C gas cooler outlet temperature
** incl. control cabinet
***without pipe outlets
Capacity range
Scope of delivery
- 2 to 6 MT compressors (transcritical) and up to 4 LT compressors (subcritical)
- Capacity control for the MT lead compressor
- Active oil management
- Receiver (83 to 285 l) with minimum level indicator
- Flash gas heat exchanger
- LT suction gas superheater
- Mechanical filters in oil line, before the HP valve, in liquid line and in LT suction line
- Filter dryer in the MT suction line
- Service and shut-off valves on all service-relevant components and pipe sections
- Pressure gauges for each pressure stage
- Pressure and temperature sensors matched to the desired control system brand
- High-end insulation executed in Armacell AF
- All pipe outlets (CuFe2P) are routed upwards.
- Safety valves mounted on valve panel, loose for on-site installation
- Fully welded heavy-duty frame incl. vibration dampers
Options
- Capacity control
- MT lead compressor: Standard or pulse width modulated
- MT lag compressor: capacity control 50/100%
- LT lead compressor: frequency inverter
- Heat recovery with 3-way valve, ball valves and insulation of discharge line, oil separator and heat exchanger, optional gas cooler bypass
- Redundant HP and MP valves
- Standstill cooling, R290
- Bypass of the filter dryer in MT suction line
- Mounted LT desuperheater or external LT desuperheater with 3-way valve and muffler
- Liquid ejector incl. liquid separator
- Active liquid subcooling
- MT and LT hot gas injection
- MT liquid injection
- Low pressure switch
- Pre-wiring
- Control cabinet, mounted or loose
- Air spring elements
- Housing for indoor and outdoor installation
Control & control cabinet
- Main switch
- Active control cabinet ventilation
- Control cabinet lighting and socket
- Power supply for closing the HP and MP valves in the event of power failure
- Shared energy metering (optional)
- Control transformer
- Surge protection (optional)
- Monitoring system (optional)
- Control technology optionally CAREL, Danfoss, WURM